Inside the UL Solutions Report on Large-Scale Fire Testing: Why Nickel-Zinc Exhibits No Thermal Runaway and Simplifies Fire Safety Compliance 

November 23, 2026
nickel-zinc battery

For data center operators, enterprise facilities managers, and mission-critical power architects, battery safety is no longer just an operational preference; it is a central regulatory requirement. As code enforcement around Energy Storage Systems (ESS) and Uninterruptible Power Supply (UPS) deployments tighten, navigating standards like NFPA 855 and the International Fire Code (IFC) can often feel complex and restrictive.  

A recent Letter Report from UL Solutions provides authoritative third-party confirmation regarding the safety profile of ZincFive’s nickel-zinc (NiZn) monobloc batteries and energy storage systems.  

Here is a breakdown of the key findings from UL Solutions, what the testing revealed, and how NiZn simplifies code compliance for next-generation power deployments.  

No Thermal Runaway Under Extreme Abuse Testing

To evaluate thermal runaway propagation in battery systems, UL Solutions performed ANSI/CAN/UL 9540A Cell-Level Abuse Testing on ZincFive monobloc batteries. The batteries were subjected to five aggressive abuse conditions designed to force thermal runaway:  

  • External thin-film heating  
  • Nail penetration  
  • Overcharge  
  • Overdischarge  
  • Short-circuiting

The Results

Under all five test conditions, ZincFive’s NiZn batteries did not undergo thermal runaway. Because the chemistry is inherently safe and did not experience a thermal runaway event, UL Solutions formally confirmed that continued higher-level testing (module, unit, and large-scale fire testing) under UL 9540A is not required.  

Everything You Need to Know About Nickel-Zinc Batteries (FAQ)

Read Post

Nickel-Zinc: Complete Exemption from Large-Scale Fire Testing (NFPA 855)

Due to the thermal runaway risks of traditional, high-energy chemistries like lithium-ion, standards like NFPA 855 typically require extensive and costly large-scale fire testing before installation. 

However, under the 2026 edition of NFPA 855, aqueous nickel-based batteries that are listed to UL 1973 are explicitly exempt from UL 9540A and large-scale fire testing. Because ZincFive’s monobloc batteries use an aqueous (water-based) electrolyte and hold an ANSI/CAN/UL 1973 Listing (File MH62563) alongside an ANSI/CAN/UL 9540 Listing (File E540538) for our DC ESS platforms, our systems fully meet this exemption.  

Whether deployed in a UPS configuration or a broader ESS architecture, ZincFive NiZn systems remove the regulatory headache of proving fire propagation safety on-site.  

Standard Mechanical Ventilation vs. Complex Suppression

 During the cell-level abuse testing, UL Solutions documented off-gassing concentrations of hydrogen gas.  As NiZn utilizes an aqueous electrolyte, hydrogen off-gassing is a natural byproduct of electrolysis during extreme operation—a characteristic shared with valve-regulated lead-acid (VRLA) and traditional nickel-based systems.  

Both ANSI/CAN/UL 1973 and ANSI/CAN/UL 9540 address this directly by requiring enclosure ventilation openings to prevent flammable gas accumulation. Furthermore, IFC Chapter 12 (Section 1207.6) and NFPA 855 (Paragraph 9.7.6) dictate standard exhaust ventilation requirements for electrochemical ESS.  

  • The Compliance Path: Rather than installing specialized, expensive explosion mitigation or burn-out rooms, site designers simply coordinate standard continuous or demand-based exhaust ventilation.  
  • The Threshold: Mechanical exhaust must be designed to maintain hydrogen gas concentrations below 25% of the Lower Flammability Limit (LFL).  

The Bottom Line for Facility Executives

When designing modern data centers and power rooms, especially for high-density AI and mission-critical workloads, safety and compliance should accelerate deployment, not slow it down. 

The UL Solutions Letter Report validates what we’ve engineered from day one: NiZn chemistry delivers ultra-high power density and continuous reliability without thermal runaway risks or burdensome fire testing requirements. 